How Photoperiod Timing Reshapes PV-Battery Sizing for Plant Factories

Written by

in

Paper digest: a study by a Shanghai Jiao Tong University team published in Energy and Buildings (In Press, JCR Q1), explained for practitioners.

Electricity costs account for 30–50% of plant factory operating expenses — a core bottleneck to scaling. The central finding of this study: photoperiod start time matters as much as PV array size for required storage capacity. In Shanghai, shifting the lighting schedule from a conventional evening start to 03:00–05:00 cuts battery capacity requirements by 40% with identical PV sizing.
PV-battery integration in plant factories
Plant factory × PV-battery: saving an entire storage system just by choosing when to turn the lights on

Highlights

  • Simulation framework: A joint PV, BES, and PFAL load optimization framework — Vertical Farm Energy Designer (VFED) — validated against a full year of operational data from Shanghai.
  • Key finding: Systematically quantified the impact of photoperiod start time on PVBES configuration — photoperiod timing matters as much as PV array sizing for energy autonomy.
  • Benchmark data: PVBES sizing benchmarks across 5 climate zones (Shanghai, Lhasa, Haikou, Harbin, Urumqi).
  • Open-source tools: Framework and datasets released for researchers and practitioners to replicate and customize for local conditions.

At a Glance

Electricity costs account for 30–50% of plant factory operating expenses — a core bottleneck to scaling. Existing PV-battery integration research for PFALs has two critical gaps: first, photoperiods are treated as fixed constraints rather than optimizable variables; second, there is a lack of empirically validated design benchmarks for specific system configurations.

This study, led by Thomas Xiong and Hua Bao at Shanghai Jiao Tong University, establishes a joint simulation-optimization framework (VFED) integrating photovoltaic generation, battery storage, and plant factory loads. Validated against a full year of measured data, the framework was applied to systematically optimize across 10,584 configuration combinations spanning five representative climate cities.

The central finding: photoperiod timing is equally critical as PV array size for achieving energy autonomy. In Shanghai, shifting the photoperiod from a conventional evening schedule to an early-morning start (03:00–05:00) reduces required battery capacity by 40% while maintaining identical PV sizing. Across five cities, the minimum system for near-energy autonomy varies dramatically: a 20-foot container PFAL (16 m² cultivation area) requires only 40 m² PV + 40 kWh storage in Lhasa, but up to 120 m² PV + 50 kWh storage in Harbin. This study provides a reproducible simulation framework and empirically grounded design benchmarks for PFAL energy system planning.

Electricity eats half the profit of a plant factory

To understand why PFALs need PV integration in the first place, let us start with a simple question: how much of the operating cost does electricity actually consume?

Food security and the rise of plant factories

Recent extreme climate events and global pandemics have exposed the vulnerability of traditional food supply chains, driving the development of Controlled Environment Agriculture (CEA). Plant Factories with Artificial Lighting (PFALs), as the most efficient form of CEA, enable year-round crop production in fully enclosed environments, completely independent of external weather conditions. This holds significant implications for urban food supply, desert agriculture, and even space farming.

However, the “enclosed” nature of PFALs means that all growth conditions must be artificially provided. LED lighting systems simulate photosynthesis, and HVAC systems manage the substantial internal heat gain — all of which demand significant electricity input. According to research data, electricity costs account for 30–50% of PFAL operating expenses, making this the primary barrier to economic viability and large-scale adoption.

The PV + storage solution

An intuitive approach emerges: if PFALs consume so much electricity, why not generate it on-site? In recent years, PV-battery energy storage systems (PVBES) have seen rapid development. In residential and industrial microgrids, optimization methodologies typically focus on demand-side management to align flexible loads with solar availability, forming mature design workflows.

In agriculture, greenhouse-oriented PV research has made notable progress: some studies achieved 25.7% energy offset through PV, while others optimized hybrid PVBES and solar thermal systems to cover 51% of the electricity load, with economic analyses showing payback periods as low as six years. However, these studies target greenhouses — whose loads are primarily driven by weather-dependent heating and cooling demands, leaving virtually no room for load shifting.

By contrast, PFALs possess a distinct advantage: the timing of artificial lighting can be flexibly adjusted without compromising crop yield. Plant growth depends on cumulative Daily Light Integral (DLI), not on specific lighting hours. This creates an unprecedented optimization space for actively coordinating photoperiods with PV generation.

The research gap

Yet existing PFAL-PVBES research suffers from two critical limitations:

  1. Overlooking temporal flexibility: Current studies treat photoperiods as fixed temporal patterns rather than optimizable variables. The conventional “nighttime photoperiod” strategy (e.g., starting at 18:00) creates a temporal mismatch between PV generation peaks and LED demand, forcing the system to store daytime solar energy in batteries for evening use — inflating storage requirements and incurring energy conversion losses.
  2. Lack of design benchmarks: For a typical 20-foot container PFAL (16 m² cultivation area), how much PV area and battery capacity are needed to achieve energy autonomy? Such concrete system sizing benchmarks are virtually absent from the literature.

This study addresses both gaps by providing an empirically validated simulation framework and multi-climate-zone design benchmarks for PFAL-PVBES systems.

One year of measured data + ten thousand enumerated configurations

The credibility of any simulation-based conclusion rests on its input data. To ensure the findings are not speculative, this study calibrated its models against a full year of operational measurements, then exhaustively enumerated over ten thousand configurations.

Integrated framework

The research team established a four-level integrated simulation-optimization framework: Vertical Farm Energy Designer (VFED).

VFED four-level integrated simulation-optimization framework
The VFED four-level framework: case setup → hybrid modeling → design optimization → economic evaluation

Level 1: Case study setup — Local meteorological data are integrated with an EnergyPlus thermal model. A demonstrative 20-foot container PFAL in Shanghai serves as the baseline case, with its parameters validated against measured data.

Level 2: Hybrid modeling — A dynamic energy flow model incorporating PV generation, BES, and PFAL loads is constructed. The PV modules use a single-diode model; the BES model accounts for charge/discharge efficiency. PV module parameters are sourced from Jinko Solar official specifications, BES parameters from CATL official specifications. Grid electricity price is simplified to a uniform fixed rate (0.096 $/kWh).

Level 3: Design optimization — A parameter sweep across photoperiod timing and system sizing is executed, ensuring hourly energy balance. Through systematic optimization, the optimal solution is identified among 10,584 configuration combinations (441 PVBES configurations × 24 photoperiod start hours).

Level 4: Economic evaluation — The optimal design is identified by minimizing the Levelized Cost of Energy (LCOE).

Operational data monitoring

The research team monitored a 20-foot container PFAL in Shanghai for a full year (January–December 2024), collecting energy consumption data for LED lighting, air conditioning, fan filter units, and fresh air units at a 1-hour resolution. Measured data reveal:

  • Total energy consumption exhibits seasonal variation: ~20 kWh/day in winter, peaking above 45 kWh/day in summer and early autumn.
  • Air conditioning is the dominant source of consumption fluctuation: <5 kWh/day in winter, up to 25 kWh/day in summer.
  • LED lighting is relatively stable: 10–20 kWh/day, adjusted according to crop growth requirements.
Shanghai container PFAL annual energy breakdown
Annual energy breakdown of the Shanghai container PFAL: HVAC drives the seasonal swings

Seasonal COP values for the air conditioning system: winter 3.94, spring 3.85, summer 2.73, autumn 2.57. The low energy consumption and high COP in winter/spring are primarily due to heat dissipation from LED and other equipment offsetting heating demand.

Optimization methodology

The study defines two key economic metrics and two energy autonomy indicators:

Levelized Cost of Energy (LCOE) = Σt [(It + Mt − Gt)/(1+r)t] ÷ Σt [Et/(1+r)t] It = investment, Mt = O&M, Gt = grid purchase cost, Et = energy delivered, r = discount rate. The other economic metric, Payback Period (PBP), equals total capital cost divided by annual savings.

Time-based Grid Dependency (TGD) — the proportion of hours within a year requiring grid supply; TGD < 5% is defined as “near-energy autonomy.” Energy-based Grid Dependency (EGD) — the proportion of annual total energy demand imported from the grid.

Industry insight: The importance of measured data
A key strength of this study is its use of a full year of operational data to validate model parameters, rather than relying on literature values or estimates. This is critical for accurately simulating air conditioning loads under different climatic conditions — daily AC consumption varies substantially across locations (from ~21 kWh/day in Shanghai to ~24 kWh/day in Haikou). Using an inaccurate load model would lead to fundamentally flawed system sizing.

One container, threefold difference between Lhasa and Harbin

How much can PVBES configuration requirements differ for the same container PFAL deployed in different cities? To answer this, the study selected five extreme climate zones for comparison — the result: a threefold difference.

Climate characteristics and energy analysis

The study selected five representative cities across China’s climate zones: Shanghai (subtropical), Harbin (severely cold), Haikou (tropical), Lhasa (plateau), and Urumqi (temperate continental).

Solar resource distribution: Lhasa receives the highest annual average (5.88 kWh/m²/day), followed by Haikou (4.72), Urumqi (4.21), with Harbin the lowest (3.81 kWh/m²/day). Seasonally, solar resource availability peaks in spring and summer, but Urumqi’s high latitude (~43.8°N) drastically shortens winter daylight hours, reducing winter solar radiation to levels comparable with Harbin (~2.2 kWh/m²/day).

Temperature distribution: Haikou exhibits the highest annual mean temperature (~25.5°C) with minimal seasonal variation; Harbin averages only ~5.7°C with extreme seasonal swings.

Five-city solar resource and configuration comparison
Five-city solar resource and temperature comparison: annual averages look similar, but the winter trough is the dividing line

Air conditioning energy projection: Haikou and Shanghai show the highest AC energy consumption (~24 and 21 kWh/day), reflecting greater cooling demand in warmer climates. Lhasa has the lowest projected AC requirement (~18 kWh/day) — despite moderate temperatures, the high-altitude nighttime cooling reduces overall cooling pressure.

Energy autonomy design boundaries

The study first addresses a critical question: can a PVBES fully meet the energy demand of a PFAL? Key finding: For a 20-foot container PFAL (16 m² cultivation area), achieving TGD < 5% near-energy autonomy requires dramatically different system configurations across cities:

CityPV Array AreaBattery Capacity
Lhasa40 m²40 kWh
Haikou50 m²45 kWh
Shanghai80 m²50 kWh
Urumqi110 m²45 kWh
Harbin120 m²50 kWh

Lhasa requires the smallest configuration, benefiting from its abundant solar resources and lower cooling demand. While Urumqi’s annual solar resource (4.21 kWh/m²/day) surpasses both Harbin (3.81) and Shanghai, its configuration requirement remains high at 110 m² — the key lies in winter: high-latitude short daylight hours reduce winter solar resources to levels comparable with Harbin (~2.2 kWh/m²/day), severely driving up the annual configuration requirement. This demonstrates that annual average solar resource alone cannot explain configuration differences — seasonal fluctuations and winter troughs are the critical bottleneck.

Impact of photoperiod timing: Analysis reveals that photoperiod start time significantly affects system reliability. Early-morning starts perform optimally. For example, in Lhasa, the mean TGD for starts at 01:00–03:00 is approximately 11%, compared to 15.01% for 17:00–19:00 starts.

Shanghai detailed analysis: In Shanghai, the minimum viable PV array area remains relatively uniform across different photoperiod start hours (86.5 ± 4.9 m²), but BES capacity requirements vary dramatically (78.5 ± 20.7 kWh). Morning photoperiods (02:00–06:00) require only 50–60 kWh storage, while afternoon photoperiods (13:00–19:00) require 80–90 kWh. By strategically aligning the photoperiod with solar peak hours, BES capacity requirements can be reduced by 40% while maintaining identical PV sizing.

Photoperiod start time impact on storage requirements
Photoperiod start time impact on storage requirements: morning vs afternoon starts differ by an entire storage system
Industry insight: The engineering significance of 40% storage reduction
A 40% reduction in battery capacity carries substantial engineering implications. For a 100 kWh storage system, this translates to approximately $12,000–18,000 in upfront capital savings.

Optimized PVBES design can slash electricity costs to one-third

Feasibility alone is insufficient — the economics must also justify the investment. To verify this, every configuration was passed through the LCOE filter.

Economic optimization results

LCOE performance: Systems designed for a 3-year payback period achieve LCOE values ranging from 0.034–0.042 $/kWh, representing a 57–61% reduction compared to the assumed grid electricity price of 0.096 $/kWh. When extending to a 5-year payback period, LCOE further decreases to 0.032–0.039 $/kWh, delivering savings of 59–67%. Lhasa consistently outperforms all other locations, attributable to its optimal combination of abundant solar radiation and moderate temperature profile — simultaneously maximizing PV generation efficiency and minimizing PFAL cooling energy requirements.

Optimal system configurations (20-foot container PFAL):

PBP TargetCityPV AreaBES CapacityLCOESavings
3-yearLhasa80 m²60–100 kWh0.034 $/kWh65% down
3-yearShanghai100 m²80–100 kWh0.042 $/kWh56% down
5-yearLhasa60–150 m²100–145 kWh0.032 $/kWh67% down
5-yearShanghai80–150 m²100–145 kWh0.039 $/kWh59% down
Five-city near-energy-autonomy system configurations
Five-city near-energy-autonomy (TGD<5%) system configuration reference
LCOE vs grid electricity price comparison
LCOE vs grid electricity price (grid baseline 0.096 $/kWh; ranges reflect optimal configurations under different photoperiods)

Optimal photoperiod start time: Nearly all cities converge on 03:00 or 04:00 as the optimal start time. This is not coincidental — with a 16-hour photoperiod, lighting ends at ~20:00, and an early-morning start allows peak LED demand to coincide with the solar generation peak from midday through 16:00. PV output directly powers the LEDs, with surplus energy stored for later use.

Industry insight: Why conventional nighttime strategies fail
Existing research often recommends shifting PFAL photoperiods to nighttime hours (e.g., starting at 18:00) to exploit off-peak electricity prices. However, when combined with PVBES, this strategy introduces a temporal mismatch penalty: daytime PV peak output cannot be directly utilized and must first be stored, then discharged in the evening — incurring approximately 15% round-trip conversion losses. In contrast, the early-morning strategy enables direct PV self-consumption during peak hours, with storage serving only as backup.

Conclusion: Shifting the photoperiod saves an entire storage system’s worth of cost

Conclusions are only as robust as the numbers behind them. To confirm that the core findings withstand scrutiny, the study conducted a systematic uncertainty assessment of the entire simulation.

Uncertainty analysis

The study systematically evaluated model uncertainties. Based on measured data, the PV model accuracy achieves R² = 0.992 (±3% error), the PFAL energy consumption model R² = 0.908 (±10% error), and the BES model is assigned ±2% error based on manufacturer specifications. Using the Root Sum of Squares method for error propagation, the composite system uncertainty is approximately ±11%. Sensitivity analyses further confirm the robustness of core conclusions: even under severe battery degradation (efficiency reduced to 80%), the 04:00 photoperiod strategy retains a 46.9%–57.8% LCOE advantage over the 13:00 strategy.

The core value of sizing-scheduling coordination

The central contribution of this study lies in establishing that photoperiod scheduling is as critical as PVBES component sizing. This finding carries significant engineering implications:

  1. Substantial expansion of the optimization space: Previously, design optimization focused solely on “how large the PV array and battery should be.” Now, “when to turn on the lights” becomes an additional optimization lever — effectively doubling the number of optimization variables and providing greater freedom to reduce system cost or enhance performance.
  2. Nonlinear reduction in storage requirements: Through active temporal alignment, BES capacity requirements can be reduced by 40%. This not only lowers upfront capital investment but also reduces battery footprint and thermal management burden. (This conclusion has been validated through battery degradation robustness testing: even at 80% efficiency, the early-morning photoperiod strategy retains a 46.9%–57.8% advantage over the conventional midday strategy — see Appendix B.)
  3. Fundamental distinction from other flexible loads: Conventional building microgrid loads are largely fixed in time, whereas PFAL loads (LED lighting) possess temporal adjustability. This unique characteristic enables PFALs to achieve energy coordination outcomes unattainable in traditional microgrids.

Regional differences and siting guidance

Lhasa (high irradiance + cold temperatures): The lowest configuration requirement. Annual average solar resource of 5.88 kWh/m²/day combined with plateau low temperatures ensures high PV generation while minimizing cooling energy. 40 m² PV + 40 kWh BES achieves near-energy autonomy.

Shanghai / Haikou (moderate irradiance + warm temperatures): Larger PV areas required. Moderate solar resources but higher cooling demand. Shanghai requires 80 m² PV + 50 kWh BES; Haikou requires 50 m² PV + 45 kWh BES.

Harbin / Urumqi (low irradiance + extreme temperatures): Higher configuration requirements. Winter solar resource declines sharply, while low temperatures (Urumqi) or high cooling demand (Harbin) drive up energy consumption. 110–120 m² PV and 50 kWh BES are needed for near-energy autonomy. (Note: This study adopts simplified seasonal-fixed COP modeling, validated against an hourly COP model: cold-region deviation −14.5%, hot-region +17.2% — all within the ±11% global uncertainty range. See Appendix A.)

Empirical coefficients per m² of cultivation area: PV requirement 2.5–7.5 m²/m² cultivation area; storage requirement 2.5–3.1 kWh/m² cultivation area.

The scaling challenge

The study reveals a critical practical constraint: the optimal PV array area (80–150 m²) far exceeds the container footprint itself (~15 m²). This gap presents two response pathways:

Pathway 1: Solve the space problem — deploy PV arrays above containers, adopt “agrivoltaic” models with elevated ground-mounted PV above PFAL installations, or utilize expansive rooftops of multi-story industrial or commercial buildings for vertical integration.

Pathway 2: Identify more feasible suboptimal solutions — under real-world land constraints, the VFED simulation platform can re-optimize within spatially bounded conditions. Typical suboptimal strategies include prioritizing storage adequacy for nighttime supply, or accepting moderately increased grid dependency (TGD relaxed from <5% to <15%) in exchange for a >50% reduction in PV footprint. Calculations show that relaxing the TGD target to 10% reduces Harbin’s PV area requirement from 120 m² to approximately 70 m², substantially improving feasibility.

When transitioning from single-unit to large-scale commercial deployment, operators can aggregate multiple cultivation modules and centralize BES to share capital costs. The VFED framework developed in this study supports such scaling analyses and scenario optimization.

Main contributions

  1. An empirically validated simulation framework and benchmark data: Based on a full year of measured data, a joint PV-storage-load simulation-optimization framework (VFED) was established, with design references across five climate zones.
  2. Systematic quantification of photoperiod scheduling impact: The early-morning photoperiod strategy (03:00–05:00) reduces BES requirements by 40% while maintaining identical energy autonomy levels, lowering LCOE to as low as 0.034 $/kWh — a 57–67% reduction compared to grid electricity prices.
  3. Identified pathways to scaling: PV array requirements (80–150 m²) typically far exceed container footprints, suggesting that future deployments should prioritize rooftop vertical integration or agrivoltaic configurations.
  4. Open-source release to advance future research: The complete VFED simulation-optimization framework has been released as open-source, inviting researchers and practitioners to further optimize and apply these models based on local climatic and economic conditions.

Appendix: Key Parameter Summary

Baseline case parameters (Shanghai 20-foot container PFAL)

CategoryParameterValue
System scaleCultivation area16 m² (20-foot standard container)
LED lightingPower density152 W/m²
LED lightingDaily energy range10–20 kWh/day
HVAC systemSeasonal COPWinter 3.94 / Spring 3.85 / Summer 2.73 / Autumn 2.57
HVAC systemDaily energyWinter <5 kWh/day; summer up to 25 kWh/day
Total energySeasonal typical valuesWinter ~20 kWh/day; summer peak >45 kWh/day
SimulationParameter space441 PVBES configs × 24 photoperiod starts = 10,584
SimulationModel validationFull-year (Jan–Dec 2024) measured data in Shanghai

Five-city system configuration reference (TGD<5%)

CityPV Array AreaBES CapacityAnnual Solar Resource
Lhasa40 m²40 kWh5.88 kWh/m²/day
Haikou50 m²45 kWh4.72 kWh/m²/day
Shanghai80 m²50 kWh4.0–4.5 kWh/m²/day
Urumqi110 m²45 kWh4.21 kWh/m²/day
Harbin120 m²50 kWh3.81 kWh/m²/day
Appendix A (fixed-COP validation): Comparison against an hourly COP model shows cold-region deviation −14.5% and hot-region +17.2%, with monthly economic impact within ±$13/month — far smaller than the savings from PVBES configuration optimization (>$3,000 per city). The fixed-COP simplification retains sufficient accuracy within the ±11% global uncertainty range.
Appendix B (battery degradation robustness): Across five battery efficiency levels (80% severe degradation to 95% high performance), the 04:00 photoperiod start consistently outperforms the 13:00 midday strategy, maintaining a 46.9%–57.8% LCOE advantage — the core conclusion is never reversed.

Reference

Photovoltaic-battery integration strategy in plant factories with artificial lighting
Thomas Xiong, Wenyi Cai, Yue Hu, Mengxuan Song, TingTing Qian*, Hua Bao*
DOI: 10.1016/j.enbuild.2026.117462 (Energy and Buildings, In Press, JCR Q1)
Affiliation: Pan-Origin Institute of Future Technology, Shanghai Jiao Tong University; Information Research Institute, Shanghai Academy of Agricultural Sciences
Open-source framework: Vertical Farm Energy Designer (VFED) — github.com/ThomasXIONG151215/vertical-farm-energy-designer
Data availability: Measurement data, model code, and optimization results are all open-source.
Planning the energy system for a plant factory or controlled-environment facility? Explore our iFEMS energy optimization toolkit, or reach us at yuankethomas@yunshi-tech.com.